Sélection des produits

for UL feeder circuits >250V

système de base 125 A (11405)     PCF: 10,43 kg CO2e

The picture may show a similar product.

Description

Référence 11405000A

CrossBoard®

système de base 125 A

3 pôles

405 mm de long, protection contre le contact

avec interface CrossLink®

Système

CrossBoard®

Avantages produit

all-round touch-safe protected busbar system up to 125A
mounting to DIN rails with no tools
simplae screwing-on to mounting plates
completly pre-assembled and ready to use

Groupe de produits 06
Sous-groupe 50
Dimensions de l'emballage 1
EAN 4021267114053
catalog page 2020 : 1.1
ECLASS 6.1 27400613
ECLASS 7.1 27400613
ETIM 4.0 EC001900
ETIM 5.0 EC001900

Homologations

Normes

IEC 61439-1:2011

UL 508

Approbations

IEC (CB) , UL , EAC

for UL feeder circuits >250V

Type: CB405-24x7

EAC Type: CB

UL file: E123577, UL category (for USA): NMTR https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com

Homologation CCC: no certification required

Données techniques

Details IEC
Normes
IEC 61439-1:2011
Electrical data IEC
Courant assigné (IEC): 125 A
Tension assignée (IEC) CA: 690 V
rated isolation voltage Ui AC: 800 V
Tension assignée de tenue aux chocs Uimp: 6 kV
rated peak withstand current  Ipk max.: 25 kA
rated short-time withstand current Icw (0.3 s) max.: 10 kA

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 6,0 W.

(The power dissipation at full load would be 9,3 W.)

Supplementary data IEC

Les valeurs suivantes ont été vérifiées par des tests sous certaines conditions. Veuillez demander ces conditions à Wöhner avant de concevoir votre armoire.

Tension maximale IEC CC: 800 V
Details UL
Normes
UL 508
for UL feeder circuits >250V
Electrical data UL
rated current (UL): 100 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
rated voltage (UL) DC: 600 V
SCCR unprotected max.: 10 kA
3 cycles (without OPD) @ 600 V AC
SCCR protected max.: 100 kA
with JDDZ fuse Class J 175 A / 600 V AC
SCCR: 100 kA with JDDZ fuse Class J 175 A / 600 V AC
65 kA with any DIVQ/7 circuit breaker 100 A / 600 V AC
100 kA with any DIVQ/7 circuit breaker 100 A / 480 V AC
Charactéristiques mécaniques
L x H x P: 405 x 160 x 45
Poids: 137,2 kg/100
Pôles: 3 pôles
degree of protection: IP20

Conseils

We recommend the use of a high DIN rail (35x15) for optimum stability and maximum load of 4 kg.
For higher loads we recommend to fix the CrossBoard® with screws on a panel.
For the use of the QUADRON®CrossBoard NH fuse switch-disconnector size 000 the CrossBoard® has to be fixed with screws on a panel.
For details please see the mounting instruction.

2 CrossBoards® mounted side by side can get a shared feeding component.

The drilling plan for mounting 2 CrossBoards® side by side is available as Dimensioned drawing #2

Links

Documentation

Accessoires

11050000A
CrossBar®
mounting rail for accessories
attachable to CrossBoard
for distribution terminals
Nouveau
Plus

11051000A
CrossBar®
mounting rail for accessories
attachable to CrossBoard
for distribution blocks
pour: Phoenix Contact PTFIX
Nouveau
Plus

Trouver votre contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com

Produits Configurateur Calcul de la plus-value métal folder for files