Product data

for design verfication according to IEC / EN 61439-1

Product description
Référence 32719000A
Désignation adaptateur de jeu de barres, 1200 A
Description 300 x 652, connexion par le bas, contact de serrage, rotation de phase 
pour Schneider Electric Compact NS1250, ComPacT NS1250
pour jeux de barres 30, 40, 60, 80, 100, 120 x 10
Courant assigné (IEC) 1 200 A
Tension assignée (IEC) CA 690 V
Tension assignée (IEC) CC 800 V
power dissipation at full load of the item 335,0 W
Type EQ185-A1600-C
Product features for design verification
Construction
10.2 Strength of materials and parts see following subitems
10.2.2 Resistance to corrosion Requirements fulfilled
Wöhner products are electrical equipment for which the respective product standard is to be applied.
The single parts made out of ferrous metals are protected efficiently against corrosion.
10.2.3 Properties of insulating materials see following subitems
10.2.3.1 Verification of thermal stability of enclosures Wöhner products do not represent an enclosure. However, the required heat resistance of 70° is fulfilled.
10.2.3.2 Verification of resistance of insulating materials to abnormal heat and fire due to internal electric effects Requirements fulfilled (glow wire test)
parts necessary to retain current carrying parts in position: 960°C
other parts: 650 °C
10.2.4 Resistance to ultra-violet (UV) radiation only applicable for outdoor installations
not relevant, since Wöhner components are generally not used as external parts
10.2.5 Lifting not relevant, since the whole assembly must be evaluated
10.2.6 Mechanical impact not relevant, only applicable for enclosures
10.2.7 Marking requirements fulfilled
10.3 Degree of protection of enclosures not relevant, only applicable for enclosures
10.4 Clearances and creepage distances the requirements are fulfilled for the single Wöhner components
10.5 Protection against electric shock and integrity of protective circuits lies within the responsibility of the assembler
10.6 Incorporation of switching devices and components lies within the responsibility of the panel builder
the requirements are fulfilled for the single Wöhner components, as long as they are used as intended and Wöhner's mounting and operating instructions are respected
10.7 Internal electrical circuits and connections lies within the responsibility of the panel builder
the requirements are fulfilled for the single Wöhner components, as long as they are used as intended and Wöhner's mounting and operating instructions are respected
10.8 Terminals for external conductors lies within the responsibility of the panel builder
the requirements are fulfilled for the single Wöhner components, as long as they are used as intended and Wöhner's mounting and operating instructions are respected
Behaviour
10.9 Dielectric properties see following subitems
10.9.1 General lies within the responsibility of the panel builder
 the requirements are fulfilled for the single Wöhner components, as long as they are used as intended and Wöhner's mounting and operating instructions are respected
10.9.2 Power-frequency withstand voltage 1000 V
1000 V
10.9.3 Impulse withstand voltage 12 kV
10.9.4 Testing of enclosures made of insulating material not relevant, since the whole assembly must be evaluated
10.9.5 External conditions of insulating material not relevant
10.10 Verification of temperature rise the single Wöhner components meet the temperature rise requirements of the the product standards as long as they are used as intended.
Additionally, evidence must be provided for the switchgear combination or for parts of it. Power dissipations of the Wöhner components can be used here.
10.11 Short-circuit withstand strength
rated peak withstand current  Ipk max.:
106 kA
rated short-time withstand current Icw (1.0 s) max.:
50 kA
10.12 Electromagnetic compatibility (EMC) lies within the responsibility of the assembler
10.13 Mechanical operation lies within the responsibility of the panel builder
the requirements are fulfilled for the single Wöhner components, as long as they are used as intended and Wöhner's mounting and operating instructions are respected

For further information see: https://www.woehner.de/fr/produits/32719.html