busbar adapter 80 A

The picture may show a similar product.

Description

Part No.: 32472 000

EQUES 60Classic

busbar adapter 80 A

3-pole

2 adjustable mounting rails

54 x 260, without leads, with terminals 16 mm², operated from behind

for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars

System

60Classic

Product group 05
Subgroup 27
pack size 4
EAN 4021267324728
ECLASS 14.0 27370304
ETIM 5.0 EC001531
ETIM 8.0 EC001531
ETIM 10.0 EC001531

Approvals

Standards

IEC 61439-1:2020

UL 508

Approvals

CSA , UL , DNV GL

for UL feeder circuits >250V

type number: EEC6080-L

EAC Type: EQ

UL file: E123577, UL category (for USA): NMTR https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com

CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org

CCC approval: no certification required

Technical data

Details IEC
Standards
IEC 61439-1:2020
Electrical data IEC
rated current (IEC): 80 A
rated voltage (IEC) AC: 690 V
rated isolation voltage Ui AC: 800 V
rated surge voltage Uimp : 6 kV

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 6.0 W.

(The power dissipation at full load would be 9.3 W.)

Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

max. permitted voltage (IEC) DC: 800 V
min. permitted operation temperature -40°C
Details UL
Standards
UL 508
for UL feeder circuits >250V
Electrical data UL
rated current (UL): 80 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
SCCR unprotected max.: 10 kA
3 cycles (without OPD) @ 600 V AC
SCCR protected max.: 100 kA
with fuse Class CF, J or T 150 A / 600 V AC
SCCR: 65 kA with any NKJH/7 type E 80 A / 480 V AC
65 kA with any DIVQ/7 circuit breaker 80 A / 480 V AC
Mechanical data
W x H x D: 54 x 260 x 63
weight: 43.8 kg/100
poles: 3-pole
for busbars: 12, 15, 20, 25, 30 x 5, 10 and section busbars
Terminal points
cage clamp connection
screw drive: PZ2
wire stripping: 11 mm
min. cross-section: 1.5 mm²
max. cross-section: 16 mm²
Md min.: 2.4 Nm
Md max.: 3.6 Nm
Material properties
halogen-free: Yes

Application notes

There must be a clearance of at least 12 mm above the article to remove it from the busbar system.

for feeder circuits as per UL508a, accessory 32974 is required

the short-circuit capacity of the combination of adapter and motor starter depends on the motor starter

for UL feeder circuits >250V

Links

Downloads

Accessories

accessories for mounting

connection accessories

further accessories

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com