Select product

for UL feeder circuits >250V

longitudinal busbar connector (01480)

The picture may show a similar product.

Description

Part No.: 01480000A

longitudinal busbar connector

40 mm

for busbars 30, 40, 80, 100 x 10

System

185Power

Product group 07
Subgroup 33
pack size 3
EAN 4021267014803
Katalogseite US US 2020 : 4.1
ECLASS 6.1 27400606
ECLASS 7.1 27400606
ETIM 4.0 EC000713
ETIM 5.0 EC000713

Approvals

Standards

IEC 61439-1:2011

UL 508

Approvals

UL , EAC

for UL feeder circuits >250V

type number: CR185-C40

EAC Type: TE-C

UL file: E123577, UL category (for USA): NMTR https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com

CCC approval: no certification required

Technical data

Details IEC
Standards
IEC 61439-1:2011
Electrical data IEC
rated voltage (IEC) AC: 690 V
The insulation performance of the article depends on the installation conditions.
Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

max. permitted voltage (IEC) AC: 1000 V
max. permitted voltage (IEC) DC: 1500 V
current capacity (IEC) max.: 750 A
the busbar connector was tested in an arrangment where the busbar supports at the connection of the 2 systems had a spacing of 200 mm

test conditions: 100x10 - 100x10 (1x 01480 + 1x 01481)
peak withstand current Ipk: 106 kA
Icw (1,0 s): 50 kA

test conditions: 80x10 - 80x10 (2x 01480)
peak withstand current Ipk: 106 kA
Icw (1,0 s): 50 kA

test conditions: 40x10 - 40x10 (1x 01480)
peak withstand current Ipk: 81 kA
Icw (1,0 s): 34 kA

test conditions: 30x10 - 30x10 (1x 01480)
peak withstand current Ipk: 81 kA
Icw (1,0 s): 34 kA
Details UL
Standards
UL 508
for UL feeder circuits >250V
Electrical data UL
rated current (UL): 700 A
rated voltage (UL) AC: 1000 V
rated frequency (UL): 50 / 60 Hz
rated voltage (UL) DC: 1000 V
SCCR unprotected max.: 42 kA
3 cycles (without OPD) @ 1000 V AC
Mechanical data
W x H x D: 47 x 40 x 49
weight: 48.0 kg/100
for busbars: 30, 40, 80, 100 x 10
permitted busbar displacement: 1
permitted spacing between systems: 11 - 14 mm

Reference

one terminal is required to connect busbars 30x10
one terminal is required to connect busbars 40x10
2 terminals are required to connect busbars 80x10

a terminal 01480 plus a terminal 01481are required to connect busbars 100x10

Links

Downloads

Accessories

01416000A
touch-safe protection shroud for longitudinal connectors
3-pole, front and rear mounting, cover width 165 mm
mounting to 2 busbar supports 01430 with a center distance of 150 mm
for busbars: 30, 40, 60, 80, 100, 120 x 10
More

01482000A
touch-safe protection shroud for longitudinal connectors
3-pole, front and rear mounting, cover width 115 mm
mounting to 2 busbar supports 01430 with a center distance of 100 mm
for busbars: 30, 40, 60, 80, 100, 120 x 10
More

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com

Products Configurator Current metal surcharges folder for files