Part No.: 36204 000A

BROOME20 30Compact

power supply 20 A

380 - 500 V AC / 24 V DC, with push-in terminals

for busbars 12 x 5, 10

NEW

System

30Compact 3P

Advantages of the product

Efficiency of 96% permits an intallation width of 49.5 mm
Short-term increase in output current by up to 300%
Self-protected at short-circuit with intelligent re-start
No pre-fuse needed
Overvoltage category III

Product group 21
Subgroup 41
pack size 1
EAN 4021267362041
ECLASS 14.0 27142325
ETIM 5.0 EC002540
ETIM 8.0 EC002540
ETIM 10.0 EC002540

Approvals

Standards

IEC 61010-2-201:2024
IEC 61204-3:2016
IEC 61000-4-2:2008
IEC 61000-6-2:2016
IEC 61000-6-4:2018
IEC 61000-3-2:2018/AMD2:2024

UL 61010-1

UL 61010-2-201

Approvals

IEC (CB) , UL

for UL feeder circuits >250V

type number: BROOME20

EAC Type: PS

UL file: E497002, UL category (for USA): NMTR. https://www.ul.com

UL file: E497002, UL category (for Canada): NMTR7. https://www.ul.com

Technical data

Details IEC
Standards
IEC 61010-2-201:2024
IEC 61204-3:2016
IEC 61000-4-2:2008
IEC 61000-6-2:2016
IEC 61000-6-4:2018
IEC 61000-3-2:2018/AMD2:2024
Electrical data IEC
rated voltage (IEC) AC: 500 V
min. operating voltage AC: 380 V
output voltage DC: 24 V
output current: 20 A
voltage control: No
typical hold-up time (400 V): 20 ms
typical hold-up time (480 V): 20 ms
separation input / output: SELV / PELV
over-voltage protection: 32 V
parallel operation possible: Yes
serial operation possible: Yes
rated frequency (IEC): 50 / 60 Hz
rated isolation voltage Ui AC: 500 V
rated surge voltage Uimp : 4 kV

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 10,8 W.

(The power dissipation at full load would be 16,9 W.)

Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

min. permitted operation temperature -25°C
max. permitted operation temperature 70°C
min. permitted temperature for transport and storage -25°C
max. permitted temperature for transport and storage 70°C
3-pole feeding at L1, L2 and L3
Details UL
Standards
UL 61010-1
UL 61010-2-201
for UL feeder circuits >250V
Electrical data UL
rated voltage (UL) AC: 500 V
min. operating voltage AC: 380 V
rated frequency (UL): 50 / 60 Hz
Mechanical data
W x H x D: 49.5 x 160 x 192
weight: 86,2 kg/100
poles: 3-pole
for busbars: 12 x 5, 10
degree of protection: IP30
for vertical busbar system: Yes
for horizontal busbar system: No
Terminal points
push-in connection
AWG12 (4 mm²)
screw drive: 0.5x3
wire stripping: 13 mm
min. cross-section: 0,2 mm²
max. cross-section: 4 mm²
  
min. cross-section UL: AWG 24
max. cross-section UL: AWG 12

Application notes

for UL feeder circuits >250V

Links (Prices, CAD data)

Downloads

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com