Select product

for UL feeder circuits >250V

power supply 10 A (36202)

The picture may show a similar product.

Description

Part No.: 36202000A

BROOME10®60Classic

power supply 10 A

400 V AC / 24 V DC, with push-in terminals

for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars

NEW

System

60Classic

Advantages of the product

efficiency of 95% permits an intallation width of 45 mm
self-protected at short-circuit with intelligent re-start
no pre-fuse needed
overvoltage capacity up to 6 kV

Product group 21
Subgroup 42
pack size 1
EAN 4021267362027
catalog page 2020 : 3.1
ECLASS 6.1 27142325
ECLASS 7.1 27142325
ETIM 4.0 EC002540
ETIM 5.0 EC002540

Approvals

Standards

IEC 61010-1:2010
IEC 61010-2-201:2013

UL 61010-1

UL 61010-2-201

Approvals

IEC (CB) , UL , EAC

for UL feeder circuits >250V

type number: BROOME 10

EAC Type: PS

UL file: E497002, UL category (for USA): NMTR. https://www.ul.com

UL file: E497002, UL category (for Canada): NMTR7. https://www.ul.com

Technical data

Details IEC
Standards
IEC 61010-1:2010
IEC 61010-2-201:2013
Electrical data IEC
rated voltage (IEC) AC: 480 V
min. operating voltage AC: 380 V
output voltage DC: 24 V
output current: 10 A
voltage control: No
typical hold-up time (400 V): 20 ms
typical hold-up time (480 V): 20 ms
separation input / output: SELV / PELV
over-voltage protection: 32 V
parallel operation possible: Yes
serial operation possible: Yes
rated frequency (IEC): 50 / 60 Hz
rated isolation voltage Ui AC: 800 V
rated surge voltage Uimp : 6 kV
Further technical data:

max. input inrush current: 1,5 A

periodic and random deviation: 50 mVpp

hold-up time (typical): 20 ms

input / output separation: SELV / PELV

output overvoltage protection: max. 32 V dc


parallel installation to increase the power:
up to 30 A without additional protection
for more than 30 A each output has to be protected by a fuse 16 A

serial installation to increase the voltage:
up to 72 V dc (note: Ab at 60 V dc and more: no SELV)
Details UL
Standards
UL 61010-1
UL 61010-2-201
for UL feeder circuits >250V
Electrical data UL
rated voltage (UL) AC: 480 V
min. operating voltage AC: 380 V
rated frequency (UL): 50 / 60 Hz
Mechanical data
W x H x D: 45 x 200 x 172
weight: 71,8 kg/100
poles: 3-pole
for busbars: 12, 15, 20, 25, 30 x 5, 10 and section busbars
degree of protection: IP30
vertical installation position: Yes
Terminal points
  

push-in terminal:
IEC:
up to 2.5 mm² re, f
up to 1.5 mm² f+AE

UL:
AWG 24 - AWG 12

Links

Downloads

Accessories

36207000A
spare part busbar adapter 25 A
busbar adapter base
for busbars: 12, 15, 20, 25, 30 x 5, 10 and section busbars
NEW
More

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com

Products Configurator Current metal surcharges folder for files