Select product

for UL feeder circuits >250V

holder for cylindrical fuses, with LED (31934)

The picture may show a similar product.

Description

Part No.: 31934000

AMBUS®Panel

holder for cylindrical fuses, with LED

Class J / 3P, box terminal 50 mm²

30 A / 600 V (21x57)

für DIN Tragschiene

System

DIN rail

Advantages of the product

large clamping range, also for two identical conductors (adjacent)
holder for label
with indicator for tripped fuse
any polarity for DC voltage applications

Product group 16
Subgroup 03
pack size 2
EAN 4021267319342
catalog page 2020 : 6.10
ECLASS 6.1 27142190
ECLASS 7.1 27142190
ETIM 4.0 EC002705
ETIM 5.0 EC002705

Approvals

Standards

IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016, Fuse system H

UL 4248-8

UL 4248-1

Approvals

CSA , UL , EAC

for UL feeder circuits >250V

type number: AJC30

EAC Type: AJC

UL file: E230163, UL category (for USA): IZLT https://www.ul.com

UL file: E230163, UL category (for Canada): IZLT7 https://www.ul.com

CSA file: 110285, CSA class: 6225-01 https://directories.csa-international.org

Technical data

for fuse links size: Class J 30 A
fuse links acc. to standard: UL 248-8
permitted power dissipation of the fuse-link: 5 W
Details IEC
Standards
IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016, Fuse system H
Electrical data IEC
min. operating voltage AC: 110 V
min. operating voltage DC: 110 V

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 0.4 W.

(The power dissipation at full load would be 0.6 W.)

for Class J fuses 1 - 30A as per UL 248-8 (21x57)

indicator light
operating voltage range: 110 - 600 V AC / DC
Details UL
Standards
UL 4248-8
UL 4248-1
for UL feeder circuits >250V
suitable for field-installed conductors
Electrical data UL
rated current (UL): 30 A
rated voltage (UL) AC: 600 V
min. operating voltage AC: 110 V
rated frequency (UL): 50 / 60 Hz
rated voltage (UL) DC: 600 V
min. operating voltage DC: 110 V
for wires UL: Cu 75°C
SCCR: 200 kA
Mechanical data
W x H x D: 108 x 115 x 69
weight: 48.6 kg/100
poles: 3-pole
Mounting: für DIN Tragschiene
degree of protection: IP20
front degree of protection: IP20
Terminal points
Not suitable for aluminium cables !
  
min. cross-section UL: AWG 18
max. cross-section UL: AWG 1/0
for wires UL: Cu 75°C
  

for applications acc. to IEC / EN :
1 wire :
Cu 0,75 - 1,0 mm², Md 2,0 - 2,5 Nm / 18 - 22 lb.in.
Cu 1,5 - 50 mm², Md 3,5 - 4,0 Nm / 31 - 35 lb.in.
2 wires (of same cross-section) :
Cu 0,75 - 1,0 mm², Md 2,0 - 2,5 Nm / 18 - 22 lb.in.
Cu 1,5 - 10 mm², Md 3,5 - 4,0 Nm / 31 - 35 lb.in.
flexible cables, directly or with wire-end ferrule
(flexible cables of max. cross-section may not fit when using wire-end ferrule)

for applications acc. to UL / CSA :
only Cu cables acc. to UL 486E 60°C/75°C
1 wire :
AWG 18 - AWG 1, Class B, Md 3,5 - 4,0 Nm / 31 - 35 lb.in.
2 wires (of identical cross-section) :
AWG 18 - AWG 8, Class B, Md 3,5 - 4,0 Nm / 31 - 35 lb.in.

Links

Downloads

Accessories

Similar products

31284000
AMBUS®Panel
holder for cylindrical fuses
Class J / 1P, box terminal 50 mm²
30 A / 600 V (21x57)
More

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com

Products Configurator Current metal surcharges folder for files