Select product

for UL feeder circuits >250V

holder for cylindrical fuses (31555)

The picture may show a similar product.

Description

Part No.: 31555000

SECUR®Panel

holder for cylindrical fuses

10 x 85 / 1P

32 A, 1500 V DC

für DIN Tragschiene

System

DIN rail

Advantages of the product

easy replacement of the fuse-link
front degree of protection IP20 always guaranteed

Product group 17
Subgroup 18
pack size 5
EAN 4021267315559
catalog page 2020 : 6.7
ECLASS 6.1 27142190
ECLASS 7.1 27142190
ETIM 4.0 EC002705
ETIM 5.0 EC002705

Approvals

Standards

IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016

UL 4248-1

UL 4248-19

Approvals

UL

type number: AES10x85

UL file: E342576, UL category (for USA): IZMR https://www.ul.com

Technical data

for fuse links size: 10x85
fuse links acc. to standard: IEC / EN 60269-6
permitted power dissipation of the fuse-link: 6 W
Details IEC
Standards
IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016
Electrical data IEC
Rated current (IEC): 32 A
rated voltage (IEC) AC: 1000 V
rated voltage (IEC) DC: 1500 V
rated surge voltage Uimp : 8 kV
The insulation performance of the article depends on the installation conditions.

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 0.2 W.

(The power dissipation at full load would be 0.3 W.)

Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

for fuse links 10x85 or 14x85 as per IEC 60269-2, -4, -6
with permitted rated power dissipations up to max. 6.0W
Details UL
Standards
UL 4248-1
UL 4248-19
Electrical data UL
rated current (UL): 30 A
rated voltage (UL) DC: 1500 V
SCCR: 15 kA
Mechanical data
W x H x D: 22.5 x 130 x 65
weight: 9.2 kg/100
poles: 1-pole
Mounting: für DIN Tragschiene
front degree of protection: IP20
Terminal points
cage clamp connection
screw drive: PZ2
wire stripping: 11 mm
min. cross-section: 0.75 mm²
max. cross-section: 25 mm²
Md min.: 2.0 Nm
Md max.: 2.5 Nm
Not suitable for aluminium cables !
  

Box terminal

for applications acc. to IEC / EN :
1 wire:
Cu 0,75 - 25 mm²
2 wires (of same cross-section):
Cu 0,75 - 10 mm²
flexible cables, directly or with wire-end ferrule
(flexible cables of max. cross-section may not fit when using wire-end ferrule)
Md 2,0 - 2,5 Nm / 18 - 22 lb.in.

for applications acc. to UL  :
only stranded Cu cables acc. to UL 486E
1 wire:
AWG 18 - AWG 4
2 wires (of identical cross-section):
AWG 18 - AWG 6
Md 2,0 - 2,5 Nm / 18 - 22 lb.in.

Reference

Min. permitted ambient temperature: -25°C (installation only at temperatures > -5°C)
Climate resistance as per IEC 61439-1, max. pollution degree 3
Please note when inserting the fuse-carrier (with or without fuse-link): insert the fuse-carrier quickly

Links

Downloads

Accessories

31558000
cylindr. fuse link 25 A
1100 V DC, gPV
14 x 85
More

31559000
cylindr. fuse link 20 A
1100 V DC, gPV
14 x 85
More

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com

Products Configurator Current metal surcharges folder for files