Select product

for UL feeder circuits >250V

switch disconnector with fuses, 3-pole (33507)

The picture may show a similar product.

Description

Part No.: 33507000

QUADRON®Panel Speed

switch disconnector with fuses, 3-pole

box terminal, with electronic fuse monitoring

size 00

double-breaking

operator independent switsching

für Montageplatte

System

Mounting plate

Advantages of the product

With spring-controlled switch mechanism for frequent switching as per utilisation category "A"
Can be locked in neutral position with up to 3 padlocks
FLAG indicator shows the switch setting
Fuses can be changed safely and without tools thanks to double-breaking main contacts
Additional visible separating section by removing the cover incl. fuses
Can be used as a mains disconnector as per IEC/EN 60204-1 (main switch)
Main switch only in combination with AC-23A/B

Product group 15
Subgroup 03
pack size 1
EAN 4021267335076
catalog page 2020 : 6.17
ECLASS 6.1 27371401
ECLASS 7.1 27371401
ETIM 4.0 EC001040
ETIM 5.0 EC001040

Approvals

Standards

IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only

Approvals

EAC

type number: QCS-NH00

EAC Type: NH

Technical data

for fuse links size: NH 000, NH 00
fuse links acc. to standard: IEC / HD 60269-2
permitted power dissipation of the fuse-link: 10 W
requirements for contact parts: Fuse links with silver-plated contact pieces recommended.
For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed.
Details IEC
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
Electrical data IEC
Rated current (IEC): 125 A
rated voltage (IEC) AC: 690 V
rated isolation voltage Ui AC: 690 V
rated surge voltage Uimp : 6 kV
Utilisation category AC (IEC 60947-3) : AC-23B (690V/125A)
AC-23A (500V/125A)
AC-22A (690V/125A)

 

Utilisation category DC (IEC 60947-3) : 2 current paths (L1,L3) in series
DC-22B (220V/125A)
cond. short-circuit current with fuses (AC): 50 kA / 690 V (125A)
approved wth fuse links of operation class: gG
Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

max. permitted voltage (IEC) AC: 725 V
utilisation categories AC-23B (690V/125A), AC-23A (500V/125A), AC-22A (690V/125A), DC-22B (220V/125A), 2 current paths (L1,L3) in series; fuses gL/gG, size 00, 690V/125A for fuse links IEC 60269-2 / DIN VDE 0636-2 size 00 up to 10W power dissipation,
When several devices are used side-by-side in continuous operation, the rated load factor specified in VDE 0660 Part 500 / EN 60 439-1, Table 1, must be observed.
Special operating conditions corresponding to IEC / EN 61439-1 may yield to foulty activations of pilot switches and fuse monitors. The operating conditions have to be considered for the analysis of status signals.
System component: degree of protection IP20 at front as per DIN EN 60529, dependent upon installation in the connection area; shock protection to DIN EN 50274


Elektronische Sicherungsüberwachung:
- Zur Erkennung von Sicherungsausfällen mit Bemessungsspannung AC 100V bis AC 690V
- Keine Hilfsenergie erforderlich; Versorgung über Netzspannung
- Hilfskontakte potentialfrei
- LED- Blinkmelder (rot/grün)
- Testtaster
- Weitere Informationen unter Downloads / Datenblatt

Mechanical data
W x H x D: 106 x 233 x 153
weight: 208.0 kg/100
poles: 3-pole
Mounting: für Montageplatte
Terminal points
Not suitable for aluminium cables !
  

Box terminal:
1.5 -70mm² flexible cables, directly or with wire-end ferrules*, depending on contour of the insulated lead 95mm² could be connectable
1.5 - 10mm² solid round
16 - 70mm² stranded round
2x10mm², 2x16mm² and 2x25mm² flexible with wire-end ferrules, identical cables placed side by side, crimping square
2x10 - 2x35mm² flexible, identical cables placed side by side square

lam. Cu. 9-13 mm wide
Terminal space 13mm x 13mm

(*flexible cables of maximum cross-section may not fit when using wire-end ferrule)

Links

Downloads

Accessories

33908000
pilot switch for monitoring the switch position
changeover 250 V AC / 5 A, 30 V DC / 4 A
for: QCS-NH00, QCS-NH1, QCS-160, QCS-320
More

33914000
connecting terminal 120 mm²
front connection
for: QCS-NH00, QCS-160
More

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com

Products Configurator Current metal surcharges folder for files