Select product

for UL feeder circuits >250V

brace terminal (01760)

The picture may show a similar product.

Description

Part No.: 01760000

CRITO®

brace terminal

Cu / Al 95 - 300 mm²

for busbars 20, 25, 30 x 5, 10 and section busbars

System

60Classic, 100Energy, centre feed unit

Product group 07
Subgroup 25
pack size 3
EAN 4021267017606
catalog page 2020 : 3.6, 5.1, 5.3
ECLASS 6.1 27141146
ECLASS 7.1 27141146
ETIM 4.0 EC000001
ETIM 5.0 EC000001

Approvals

Standards

IEC 61439-1:2011
IEC 60999-1:1999
IEC 60999-2:2003

UL 508

Approvals

CSA , UL , DNV GL , EAC

type number: 529

EAC Type: TE-B

UL file: E123577, UL category (for USA): NMTR2 https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR8 https://www.ul.com

CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org

CCC approval: no certification required

Technical data

Details IEC
Standards
IEC 61439-1:2011
IEC 60999-1:1999
IEC 60999-2:2003
Electrical data IEC
Rated current (IEC): 500 A
rated voltage (IEC) AC: 690 V
The insulation performance of the article depends on the installation conditions.
rated peak withstand current  Ipk max.: 81.4 kA
rated short-time withstand current Icw (1.0 s) max.: 26.1 kA
Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

max. permitted voltage (IEC) AC: 1000 V
max. permitted voltage (IEC) DC: 1500 V
current capacity (IEC) max.: 600 A
Details UL
Standards
UL 508
suitable for field-installed conductors
Electrical data UL
rated current (UL): 420 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
for wires UL: Cu 75°C
SCCR: 65 kA
Mechanical data
W x H x D: 40 x 49 x 88
weight: 42.5 kg/100
for busbars: 20, 25, 30 x 5, 10 and section busbars
Terminal points
screw clamp connection
screw drive: S8
wire stripping: 38 mm
min. cross-section: 95 mm²
max. cross-section: 300 mm²
Md min.: 24.0 Nm
Md max.: 36.0 Nm
Suitable for aluminium cables.
When using aluminium cables, observe the maintenance instructions.
torque Alu: Alu: Md 30 - 36 Nm
  
min. cross-section UL: AWG 3/0
max. cross-section UL: MCM 600
torque (UL): 266 lb-in
for wires UL: Cu 75°C
  

for applications acc. to IEC / EN :
Cu 95 - 300 mm² stranded round cables and stranded sectored cables as well as flexible cables (directly)
Cu 240 - 300 mm² fine stranded flexible cables (directly)
Al 120 - 300 mm² stranded round cables and stranded sectored cables
Al 120 - 240 mm² solid sectored cables

for applications acc. to UL / CSA :
Cu 95 - 300 mm² / AWG 3/0 - MCM 600

Links

Downloads

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com

Products Configurator Current metal surcharges folder for files