Select product

for UL feeder circuits >250V

adapter 160 A (32691)

The picture may show a similar product.

Description

Part No.: 32691000A

EQUES®CrossBoard

adapter 160 A

90 x 160

for ABB Tmax XT2, Allen-Bradley 140G-H, Eaton NZM1, Schneider Electric NSXm

with CrossLink® interface

System

CrossBoard®

Advantages of the product

Capable of feeding and bridging two CrossBoards simultaneously.

Product group 05
Subgroup 30
pack size 1
EAN 4021267326913
catalog page 2020 : 1.4
ECLASS 6.1 27370304
ECLASS 7.1 27370304
ETIM 4.0 EC001531
ETIM 5.0 EC001531

Approvals

Standards

IEC 61439-1:2011

UL 508

Approvals

UL , EAC

for UL feeder circuits >250V

type number: EQ90-AB

EAC Type: EQ

UL file: E123577, UL category (for USA): NMTR https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com

CCC approval: no certification required

Technical data

Details IEC
Standards
IEC 61439-1:2011
Electrical data IEC
Rated current (IEC): 160 A
rated voltage (IEC) AC: 690 V
rated isolation voltage Ui AC: 800 V
rated surge voltage Uimp : 6 kV
short-circuit withstandability: the short-circuit capacity of the combination of adapter and MCCB depends on the MCCB

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 6,3 W.

(The power dissipation at full load would be 9,8 W.)

Folgende notwendige Reduktionen wurden durch Prüfungen ermittelt:
Leistungsschalter Eaton (bei Lufttemperatur 25°C):

  • Eaton NZM1, Leitungsabgang unten: 160 A
  • Eaton NZM1, Leitungsabgang oben: 160 A

Leistungsschalter Schneider Electric:

  • Schneider Electric NSXm, Leitungsabgang unten: 152 A
  • Schneider Electric NSXm, Leitungsabgang oben: 152 A
Details UL
Standards
UL 508
for UL feeder circuits >250V
Electrical data UL
rated current (UL): 100 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
SCCR unprotected max.: 10 kA
3 cycles (without OPD) @ 600 V AC
SCCR protected max.: 100 kA
SCCR: 100 kA with any DIVQ/7 circuit breaker 125 A / 480 V AC
42 kA with any DIVQ/7 circuit breaker 125 A / 600 V AC
Mechanical data
W x H x D: 90 x 160 x 45
weight: 40,0 kg/100
poles: 3-pole

Links

Downloads

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com