Description

Part No.: 33422000

QUADRON®60Classic

busbar mounted fuse holder Class J

for fuse links Class J 35 - 60 A (27x60)

3P, with box terminal

connection top or bottom

for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars

System

60Classic

Advantages of the product

the product is based on the UL approval in category IZLT2 also listed in category NMTR (file E123577)

CrossLink® adapter technology
Fast and safe conversion of the connection for top or bottom; the parts under voltage remain shock protected Simple and safe clicking into place and making contact
Safe connection through shock protection split into 2
Busbar supports for flat busbars can be mounted above each other

Product group 16
Subgroup 24
pack size 1
EAN 4021267334222
catalog page 2020 : 3.21
ECLASS 6.1 27142190
ECLASS 7.1 27142190
ETIM 4.0 EC002705
ETIM 5.0 EC002705

Approvals

Standards

IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016, Fuse system H

UL 4248-8

UL 4248-1

Approvals

UL , EAC

for UL feeder circuits >250V

type number: QCC-ClassJ60A

EAC Type: AJC

UL file: E230163, UL category (for USA): IZLT2 https://www.ul.com

UL file 2: E123577, UL category+ (for USA): NMTR https://www.ul.com

UL file: E230163, UL category (for Canada): IZLT8 https://www.ul.com

UL file 2: E123577, UL category+ (for Canada): NMTR7 https://www.ul.com

Technical data

for fuse links size: Class J 60 A
fuse links acc. to standard: UL 248-8
permitted power dissipation of the fuse-link: 7 W
Details IEC
Standards
IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016, Fuse system H

Electrical data

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 2,3 W.

(The power dissipation at full load would be 3,5 W.)

System component: degree of protection IP30 at front as per DIN EN 60529, degree of protection near terminal depends on installation
adapter module: front side degree of protection IP20 as per DIN EN 60529 (finger-safe)
Details UL
Standards
UL 4248-8
UL 4248-1
for UL feeder circuits >250V
suitable for field-installed conductors
Electrical data UL
rated current (UL): 60 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
rated voltage (UL) DC: 600 V
for wires UL: Cu 75°C
SCCR: 200 kA
Mechanical data
W x H x D: 106 x 200 x 135
weight: 135,0 kg/100
poles: 3-pole
for busbars: 12, 15, 20, 25, 30 x 5, 10 and section busbars

Busbar connector: externally tensioned contacting, convenient click mechanism, simple conversion of the combination bases from 5 to 10mm-thick busbars

Terminal points
Not suitable for aluminium cables !
  
min. cross-section UL: AWG 14
max. cross-section UL: AWG 2/0
for wires UL: Cu 75°C
  

AWG 12 - AWG 2/0 stranded, equivalent 3,3 - 67,4 mm²
AWG 14 - AWG 10 solid, equivalent 215 - 5,3 mm²

Links

Downloads

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com

Products Configurator Current metal surcharges folder for files