Select product

for UL feeder circuits >250V

busbar mounted fuse holder Class J (31970)

The picture may show a similar product.

Description

Part No.: 31970000

AMBUS®60Classic

busbar mounted fuse holder Class J

for fuse links Class J 35 - 60 A (27x60), with LED

3P, complete solution based on busbar adapter

connection bottom

for busbars 12, 15, 20, 25, 30 x 5, 10 and section busbars

System

60Classic

Product group 16
Subgroup 24
pack size 1
EAN 4021267319700
catalog page 2020 : 3.21
ECLASS 6.1 27142190
ECLASS 7.1 27142190
ETIM 4.0 EC002705
ETIM 5.0 EC002705

Approvals

Standards

IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016, Fuse system H

UL 4248-8

UL 508

Approvals

CSA , UL , EAC

type number: EEC6080-L + AJC60

EAC Type: AJC

UL file: E230163, UL category (for USA): IZLT https://www.ul.com

UL file 2: E123577, UL category+ (for USA): NMTR https://www.ul.com

UL file: E230163, UL category (for Canada): IZLT7 https://www.ul.com

CSA file: 110285, CSA class: 3211-37 https://directories.csa-international.org

Technical data

for fuse links size: Class J 60 A
fuse links acc. to standard: UL 248-8
permitted power dissipation of the fuse-link: 7 W
Details IEC
Standards
IEC 60269-1:2006 + A1:2009 + A2:2014
IEC 60269-2:2013 + A1:2016, Fuse system H

Electrical data

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 6,8 W.

(The power dissipation at full load would be 10,7 W.)

Details UL
Standards
UL 4248-8
UL 508
Electrical data UL
rated current (UL): 60 A
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
rated voltage (UL) DC: 600 V
for wires UL: Cu 75°C
SCCR: 100 kA
Mechanical data
W x H x D: 126 x 200 x 157
weight: 131,0 kg/100
poles: 3-pole
for busbars: 12, 15, 20, 25, 30 x 5, 10 and section busbars
Terminal points
Not suitable for aluminium cables !
for wires UL: Cu 75°C
  

for applications acc. to IEC / EN :
1 wire : Cu 6 - 50 mm², Md 3,5 - 4,0 Nm / 31 - 35 lb.in.
2 wires (of same cross-section) : Cu 6 - 16 mm², Md 3,5 - 4,0 Nm / 31 - 35 lb.in.
flexible cables, directly or with wire-end ferrule
(flexible cables of max. cross-section may not fit when using wire-end ferrule)

for applications acc. to UL / CSA :
only Cu cables acc. to UL 486E
1 wire : AWG 14 - AWG 1, Class C, Md 4,0 Nm / 35 lb.in.
2 wires (of identical cross-section) :  AWG 14 - AWG 6, Class C, Md 4,0 Nm / 35 lb.in.

Links

Downloads

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com

Products Configurator Current metal surcharges folder for files