Select product

for UL feeder circuits >250V

universal busbar support UL (01357)

The picture may show a similar product.

Description

Part No.: 01357000

universal busbar support UL

4-pole, with internal screw holes

for busbars 12, 20, 30 x 5, 10

System

60Classic

Advantages of the product

With internal screw holes
can also be used as centre support

Product group 06
Subgroup 12
pack size 10
EAN 4021267013578
catalog page 2020 : 3.1
ECLASS 6.1 27400607
ECLASS 7.1 27400607
ETIM 4.0 EC001166
ETIM 5.0 EC001166

Approvals

Standards

IEC 61439-1:2011

UL 508

Approvals

UL , DNV GL , EAC

for UL feeder circuits >250V

type number: S62015-L

EAC Type: SB

UL file: E123577, UL category (for USA): NMTR https://www.ul.com

UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com

CCC approval: no certification required

Technical data

Details IEC
Standards
IEC 61439-1:2011
Electrical data IEC
rated voltage (IEC) AC: 800 V
rated frequency (IEC): 50 / 60 Hz
rated isolation voltage Ui AC: 1000 V
rated surge voltage Uimp : 8 kV
The insulation performance of the article depends on the installation conditions.

power dissipation of the article:

The power dissipation at a typical load of 80 % results to 0,0 W.

(The power dissipation at full load would be 0,0 W.)

Supplementary data IEC

The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel.

max. permitted voltage (IEC) DC: 1500 V
Kurzschlussfestigkeit nach IEC:
3-phasiger KS:
Stoßstromfestigkeit > 45 kA bei Schienenträgerabstand 400 mm
Stoßstromfestigkeit > 50 kA bei Schienenträgerabstand 250 mm
1-phasiger KS
Stoßstromfestigkeit > 36 kA bei Schienenträgerabstand 400 mm
Details UL
Standards
UL 508
for UL feeder circuits >250V
Electrical data UL
rated voltage (UL) AC: 600 V
rated frequency (UL): 50 / 60 Hz
SCCR unprotected max.: 22 kA
400 mm support spacing
Mechanical data
W x H x D: 21 x 272 x 51
weight: 19,7 kg/100
poles: 3-pole+N
for busbars: 12, 20, 30 x 5, 10

Reference

To maintain the increased air and creepage sections as per UL508A, the spacer is to be used.

Links

Downloads

Accessories

01131000
end cover
for busbar supports 01357 and 01485 (1x 01131 = 1 left + 1 right cover)
More

01359000A
spacer
suitable for 01357
for UL applications
More

Find your contact

to the contact site

Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental

Order hotline (Germany)
+49 9563 751 161
order@woehner.de

Technical hotline (Germany)
+49 9563 751 260
support@woehner.com

Products Configurator Current metal surcharges folder for files