Company
Innovations
Products
The picture may show a similar product.
Part No.: 11900000A
CrossBoard®
basic system 250 A
3-pole
900 mm long, touch-safe protected
when fixing on a mounting plate, article 01585 is additionally required
with CrossLink® interface
NEW
System
CrossBoard® 125A / 250A
Advantages of the product
touch-safe protected busbar system up to 250 A
rear feedable
plug and play
easy to screw to mounting plates
completely pre-assembled and immediately ready for use
Product group | 06 |
Subgroup | 50 |
pack size | 1 |
EAN | 4021267119003 |
ECLASS 6.1 | 27400613 |
ECLASS 7.1 | 27400613 |
ETIM 4.0 | EC001900 |
ETIM 5.0 | EC001900 |
Standards
IEC 61439-1:2020
UL 508
Approvals
IEC (CB) , UL
for UL feeder circuits >250V
type number: CB-XL-900-24x16
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CCC approval: no certification required
Details IEC | |
Standards | |
IEC 61439-1:2020 |
Electrical data IEC | |
rated current (IEC): | 250 A |
rated voltage (IEC) AC: | 690 V |
rated isolation voltage Ui AC: | 800 V |
rated surge voltage Uimp : | 6 kV |
rated peak withstand current Ipk max.: | 30 kA |
rated short-time withstand current Icw (0.1 s) max.: | 15 kA |
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
max. permitted voltage (IEC) DC: | 800 V |
Details UL | |
Standards | |
UL 508 |
for UL feeder circuits >250V |
Electrical data UL | |
rated current (UL): | 250 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
rated voltage (UL) DC: | 600 V |
SCCR unprotected max.: | 10 kA |
3 cycles (without OPD) @ 600 V AC | |
SCCR protected max.: | 100 kA |
SCCR: |
100 kA with JDDZ fuse Class J 400 A / 600 V AC
65 kA with any DIVQ/7 circuit breaker 400 A / 480 V AC |
Mechanical data | |
W x H x D: | 900 x 160 x 45 |
weight: | 338,5 kg/100 |
poles: | 3-pole |
degree of protection: | IP20 |
Reference |
Crossboards before production date November 2024 also suitable for 250 A (IEC + UL). Confirmation |
for UL feeder circuits >250V |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com