Company
Innovationen
Products
The picture may show a similar product.
Part No.: 33507000
QUADRON®Panel Speed
switch disconnector with fuses, 3-pole
box terminal, with electronic fuse monitoring
size 00
double-breaking
operator independent switching (snap-action mechanism)
for mounting plate
System
Panel
Advantages of the product
With spring-controlled switch mechanism for frequent switching as per utilisation category "A"
Can be locked in neutral position with up to 3 padlocks
FLAG indicator shows the switch setting
Fuses can be changed safely and without tools thanks to double-breaking main contacts
Additional visible separating section by removing the cover incl. fuses
Can be used as a mains disconnector as per IEC/EN 60204-1 (main switch)
Main switch only in combination with AC-23A/B
Product group | 15 |
Subgroup | 03 |
pack size | 1 |
EAN | 4021267335076 |
ECLASS 6.1 | 27371401 |
ECLASS 7.1 | 27371401 |
ETIM 4.0 | EC001040 |
ETIM 5.0 | EC001040 |
Standards
IEC 60947-1:2020
IEC 60947-3:2020 AC ratings only
type number: QCS-NH00
for fuse links size: | NH 000, NH 00 |
fuse links acc. to standard: | IEC / HD 60269-2 |
permitted power dissipation of the fuse-link: | 10 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
Details IEC | |
Standards | |
IEC 60947-1:2020 IEC 60947-3:2020 AC ratings only |
Electrical data IEC | |
rated current (IEC): | 125 A |
rated voltage (IEC) AC: | 690 V |
rated isolation voltage Ui AC: | 690 V |
rated surge voltage Uimp : | 6 kV |
Utilisation category AC (IEC 60947-3) : | AC-23B (690V/125A) AC-23A (500V/125A) AC-22A (690V/125A)
|
Utilisation category DC (IEC 60947-3) : | 2 current paths (L1,L3) in series DC-22B (220V/125A) |
cond. short-circuit current with fuses (AC): | 50 kA / 690 V (125A) |
approved wth fuse links of operation class: | gG |
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
max. permitted voltage (IEC) AC: | 725 V |
utilisation categories AC-23B (690V/125A), AC-23A (500V/125A), AC-22A (690V/125A), DC-22B (220V/125A), 2 current paths (L1,L3) in series; fuses gL/gG, size 00, 690V/125A for fuse links IEC 60269-2 / DIN VDE 0636-2 size 00 up to 10W power dissipation, | |
When several devices are used side-by-side in continuous operation, the rated load factor specified in VDE 0660 Part 500 / EN 60 439-1, Table 1, must be observed. Special operating conditions corresponding to IEC / EN 61439-1 may yield to foulty activations of pilot switches and fuse monitors. The operating conditions have to be considered for the analysis of status signals. |
|
System component: degree of protection IP20 at front as per DIN EN 60529, dependent upon installation in the connection area; shock protection to DIN EN 50274 | |
|
Mechanical data | |
W x H x D: | 106 x 233 x 153 |
weight: | 208,0 kg/100 |
poles: | 3-pole |
Mounting: | for mounting plate |
Terminal points | |
Not suitable for aluminium cables ! | |
Box terminal: |
Not suitable for aluminium cables ! | |
permitted power dissipation of the fuse-link: | 10 W |
requirements for contact parts: |
Fuse links with silver-plated contact pieces recommended. For fuse links with nickel-plated contact pieces, a reduction factor of 0.8 is to be observed. |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com