Company
Innovationen
Products
for UL feeder circuits >250V
The picture may show a similar product.
Part No.: 11225000A
CrossBoard®
basic system 125 A
3-pole
225 mm long, touch-safe protected
with CrossLink® interface
System
CrossBoard® 125A / 250A
Advantages of the product
all-round touch-safe protected busbar system up to 125 A
mounting to DIN rails with no tools
simple screwing-on to mounting plates
completely pre-assembled and ready to use
Product group | 06 |
Subgroup | 50 |
pack size | 1 |
EAN | 4021267112257 |
ECLASS 6.1 | 27400613 |
ECLASS 7.1 | 27400613 |
ETIM 4.0 | EC001900 |
ETIM 5.0 | EC001900 |
Standards
IEC 61439-1:2020
UL 508
Approvals
IEC (CB) , UL
for UL feeder circuits >250V
type number: CB225-24x7
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CCC approval: no certification required
Details IEC | |
Standards | |
IEC 61439-1:2020 |
Electrical data IEC | |
rated current (IEC): | 125 A |
rated voltage (IEC) AC: | 690 V |
rated isolation voltage Ui AC: | 800 V |
rated surge voltage Uimp : | 6 kV |
rated peak withstand current Ipk max.: | 25 kA |
rated short-time withstand current Icw (0.3 s) max.: | 10 kA |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 3,4 W.
(The power dissipation at full load would be 5,3 W.)
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
max. permitted voltage (IEC) DC: | 800 V |
Details UL | |
Standards | |
UL 508 |
for UL feeder circuits >250V |
Electrical data UL | |
rated current (UL): | 100 A |
rated voltage (UL) AC: | 600 V |
rated frequency (UL): | 50 / 60 Hz |
rated voltage (UL) DC: | 600 V |
SCCR unprotected max.: | 10 kA |
3 cycles (without OPD) @ 600 V AC | |
SCCR protected max.: | 100 kA |
with JDDZ fuse Class J 175 A / 600 V AC |
SCCR: |
65 kA with any DIVQ/7 circuit breaker 100 A / 600 V AC
100 kA with any DIVQ/7 circuit breaker 100 A / 480 V AC 100 kA with JDDZ fuse Class J 175 A / 600 V AC |
Mechanical data | |
W x H x D: | 225 x 160 x 45 |
weight: | 79,8 kg/100 |
poles: | 3-pole |
degree of protection: | IP20 |
Reference |
We recommend the use of a high DIN rail (35x15) for optimum stability and maximum load of 4 kg. |
for UL feeder circuits >250V |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com