Company
Innovationen
Products
for UL feeder circuits >250V
The picture may show a similar product.
Part No.: 01614000
flexible copper busbar, plain, insulated
5x 40 x 1
736 A, length 2 m
Advantages of the product
The laminated Cu busbars considerably reduce the effort of connecting busbars. The bending devices required for solid copper busbars are unnecessary. The 2mm-thick insulation means that no additional covering is required.
Product group | 06 |
Subgroup | 81 |
pack size | 1 |
EAN | 4021267016142 |
ECLASS 6.1 | 27370303 |
ECLASS 7.1 | 27370303 |
ETIM 4.0 | EC001522 |
ETIM 5.0 | EC001522 |
Standards
IEC 61439-1:2020
UL 758
UL 67
Approvals
UL
for UL feeder circuits >250V
type number: 5x40x1
UL file: E197039, UL category (for USA): QEUY2 https://www.ul.com
UL file 2: E481423, UL category+ (for USA): AVLV2 https://www.ul.com
UL file: E197039, UL category (for Canada): QEUY8 https://www.ul.com
CCC approval: no certification required
Details IEC | |
Standards | |
IEC 61439-1:2020 |
Electrical data IEC | |
rated current (IEC): | 736 A |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 73,0 W.
(The power dissipation at full load would be 114,1 W.)
Supplementary data IEC | |
The following values have been verified with tests under certain conditions. Please ask Wöhner for this conditions before designing your panel. |
current at 30 K : |
541 A |
current at 40 K: | 644 A |
current at 50 K : |
736 A |
current at 60 K: | 818 A |
current at 70 K: | 894 A |
Details UL | |
Standards | |
UL 758
UL 67 |
for UL feeder circuits >250V |
capacity at 50 K: | 805 A |
Mechanical data | |
W x H x D: | 44 x 9 x 2000 |
weight: | 373,0 kg/100 |
cross-section: | 200 mm² |
short-circuit withstandability: | see product description of the used busbar support |
capacity depending on the permitted temperature rise of flexible copper busbar without impact of additional heat sources:
|
|
notice the temperature stability of the insulation of 105 °C take conductors with required cross-section for connection to the products and devices (acc. to relevant standards or manufacturer instructions) |
|
for UL feeder circuits >250V |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com