Společnost
Innovations
Produkty
Obrázek může zobrazovat podobný produkt.
Part No.: 32682 000A
EQUES CrossBoard
adaptér 32 A
1 pevná DIN lišta, s vodiči AWG 10 (6 mm²)
45 x 160
s CrossLink® rozhraním
stock sale
date of phase-out: 31.12.2025
Auslaufartikel; Follower: 32684000A
System
CrossBoard® 125A / 250A, CrossBoard® 800 A
Advantages of the product
Conductor ends ultrasonic compressed.
Click mechanism when pushing onto the CrossBoard®.
| Produktová skupina | 05 |
| Podskupina | 21 |
| velikost balení | 1 |
| EAN | 4021267326821 |
| ECLASS 14.0 | 27370304 |
| ETIM 5.0 | EC001531 |
| ETIM 8.0 | EC001531 |
| ETIM 10.0 | EC001531 |
Standardy
IEC 61439-1:2020
UL 508
Schválení dle norem
IEC (CB) , UL
for UL feeder circuits >250V
typové číslo: EQ45-AC
EAC Type: EQ
UL file: E123577, UL category (for USA): NMTR https://www.ul.com
UL file: E123577, UL category (for Canada): NMTR7 https://www.ul.com
CCC schválení: certifikace není vyžadována
| Detaily IEC | |
| Standardy | |
| IEC 61439-1:2020 |
| Elektrické údaje IEC | |
| Jmenovitý proud (IEC): | 32 A |
| jmenovité napětí (IEC) AC: | 690 V |
| jmenovité izolační napětí Ui AC: | 800 V |
| jmenovité přepětí Uimp : | 6 kV |
power dissipation of the article:
The power dissipation at a typical load of 80 % results to 1,3 W.
(The power dissipation at full load would be 2,1 W.)
| Detaily UL | |
| Standardy | |
| UL 508 |
| for UL feeder circuits >250V |
| Elektrické údaje UL | |
| jmenovitý proud (UL): | 30 A |
| jmenovité napětí (UL) AC: | 600 V |
| jmenovitá frekvence (UL): | 50 / 60 Hz |
| SCCR unprotected max.: | 5 kA |
| 3 cycles (without OPD) @ 600 V AC | |
| SCCR protected max.: | 65 kA |
| SCCR: | 65 kA with any NKJH/7 Comb. Motor Controller 32 A / 480 V AC |
| Mechanické údaje | |
| Š x V x H: | 45 x 160 x 45 |
| hmotnost: | 14,0 kg/100 |
| póly: | 3-pólový |
| Vlastnosti materiálu | |
| halogen-free: | Yes |
|
For compact mounting of complete motor circuits with commercially available switchgear and safe mechanical and electrical connection to the CrossBoard®. |
|
|
the short-circuit capacity of the combination of adapter and motor starter depends on the motor starter |
|
| for UL feeder circuits >250V |
Find your contact
to the contact site
Wöhner GmbH & Co. KG
Elektrotechnische Systeme
Mönchrödener Str. 10
96472 Rödental
Order hotline (Germany)
+49 9563 751 161
order@woehner.de
Technical hotline (Germany)
+49 9563 751 260
support@woehner.com